{}

Our Brands

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.
Search FAQs
What is meant by thermal current rating (Ith) for Contactor "D" or "F" type ?
It means the rated current that this contactor can switch for Load category AC1 (thermal loads),

Example: LC1D09 is 9 A on AC3 and its thermal current (Ith = 20 to 25 A) (this means it can switch up to 20 or 25 A for loads of AC1

Schneider Electric United Arab Emirates

What is meant by thermal current rating (Ith) for Contactor "D" or "F" type ?
It means the rated current that this contactor can switch for Load category AC1 (thermal loads),

Example: LC1D09 is 9 A on AC3 and its thermal current (Ith = 20 to 25 A) (this means it can switch up to 20 or 25 A for loads of AC1

Schneider Electric United Arab Emirates

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.