{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.
Search FAQs
What should parameter bFr be set to if you are using a 50hz 400vac motor?
Issue:
Setting up bFr parameter for a 50hz 400vac motor.

Product Line:
ALTIVAR ATV61

Environment:
All

Cause:
Installation / Setup

Resolution:
Drive settings for bFr, nPr, UnS , nCr and nSP settings,  should match the motor nameplate.
in this case bFr will be set to 50hz and UnS will be set to 400vac

Schneider Electric United Arab Emirates

Attachment(s)
atv61_programming_manual_en_1760649_08.pdf [4.35 MB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: