{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.
Search FAQs
Does the ATS01 softstart require external thermal overload protection?
Issue:
Is an external thermal overload protection needed to be installed with an ATS01?

Product Line:
ATS01, Altistart 01

Environment:
All

Cause:
N/A

Resolution:
The ATS01 softstart does not provide motor overload protection.  Separate overload thermal protection should be added to the power circuit.  This typically is done with a motor starter upstream of the ATS01.

Schneider Electric United Arab Emirates

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: