{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.

Search FAQs

What is the risk of reverse feeding Compact NSX HB1/HB2 MCCB?

For "HB" Compact NSX MCCBs, it is mandatory to supply the circuit breaker via its upstream. The high breaking performance cannot be reached if the "HB" NSX MCCB was reverse fed because we risk arcing between poles. Thus, restrict reverse feeding for this MCCB as illustrated in the attached Compact NSX 2016 catalogue extract.

Schneider Electric United Arab Emirates

Attachment(s)

Extract - Compact NSX Catalogue 2016.pdfExtract - Compact NSX Catalogue 2016.pdf [115.8 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: