Does SBEF stands for Standby Earth Fault protection function can be achieved on LV breakers?
This function can be done using Protection relays like Sepam,and can not be done in Micrologic.

Normally, The standby earth fault protection for LV breaker is achieved on the MV side ,so if the LV breaker fails to sense it,the upstream MV protection relay will back up it,and trip the MV breaker.

Schneider Electric United Arab Emirates

Does SBEF stands for Standby Earth Fault protection function can be achieved on LV breakers?
This function can be done using Protection relays like Sepam,and can not be done in Micrologic.

Normally, The standby earth fault protection for LV breaker is achieved on the MV side ,so if the LV breaker fails to sense it,the upstream MV protection relay will back up it,and trip the MV breaker. 

Schneider Electric United Arab Emirates

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.