What is the Restricted earth fault protection and how to implement on Low Voltage ?
The restricted earth fault protection (ANSI 64REF) can be applied if the downstream power system neutral is earthed at the transformer (document attached).
This is a differential protection function that detects the difference between residual currents measured at the neutral earthing point and at the three-phase output of the transformer.
Please find attached document describing how to implement the estricted earth fault protection  with Masterpact Micrologic 6.0

Schneider Electric United Arab Emirates

Attachment(s)
technical_bulletin18_v4 Restrited Earth Fault.pdf [482.87 KB]