{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.
Search FAQs
How does the scaling configuration in Modbus configuration work?
The scaling calculation is based on differentiation. Example:
The frequency is internally (in the relay) stored as an integer value which also holds three decimal places, that is, 50.000 Hz is represented as 50000. This is a value too large to be represented with 16 bits (signed integer). Frequency is by default scaled with the points: (x1, y1) = (0, 0) and (x2, y2) = (10, 1) enabling it to be sent over Modbus.

See example calculation in attachment

Schneider Electric United Arab Emirates

Attachment(s)
slope.JPG.jpg [15.64 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: