{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.

Search FAQs

What is the function of the terminal number B2 & B4 for compact NSX?

B4 (auto-power supply) is a permanent power supply to help to finish the action of opening (and internal spring compression), in case of short pulse on BP of opening command.

B2 is the reset of the motor mechanism in case of tripping. The contact SDE is add to forbidden
the reset of the motor mechanism in case of tripping of the circuit breaker due to electrical fault (trip from trip unit...)

Schneider Electric United Arab Emirates

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: