Characteristics of the inverse time-delay over-current opening releases at the reference temperature of Acti 9 iC60 circuit breakers based on IEC 60898-1 and IEC 60947-2 specifications
The derating table (attached) for the iC60 devices are based on testing with respect to IEC 60898-1 and IEC 60947-2 requirements.

Standard IEC 60898-1:
  • Testing is to be done at temperature reference 30°C
  • Conventional non-tripping current 1.13 x In
  • Conventional tripping current 1.45 x In
  • Conventional time 1h
 
Standard IEC 60947-2:
  • Conventional non-tripping current 1.05 x In
  • Conventional tripping current 1.3 x In
  • Conventional time 1h
  • Each manufacturer defines the ambient reference temperature.
50°C for MCB compliant with both standards (IEC 60898-1 and IEC 60947-2)
40°C for MCB compliant only with IEC 60947-2
 
Furthermore, the manufacturer is responsible to include the reference temperature of the test at rated current, printed on the device as follows:

For more information concerning the 2 standards, please visit the blog:
 
https://blog.schneider-electric.com/energy-regulations/2014/02/06/iec-60898-1-iec-60947-2-tale-two-standards/

Schneider Electric United Arab Emirates

Attachment(s)
Acti9_AmbientTemp.pdf [264.12 KB]
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.