{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How are unused channels wired to eliminate fault indication on the 140AVI03000 analog input module ?

For each unused analog input channel, jumper the INPUT(+) terminal to the INPUT(-) terminal and configure those channels to one of the bipolar voltage input ranges (+/- 5V or +/-10V).

Schneider Electric Australia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: