{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

How can we help you today?

What happens to the data points rtH, rtHI, and ptH on the ATV61 and ATV71 drives when it exceeds its maximum value of 65536 Hours?

Article available in these languages: Spanish

Issue:
Data points rtH, rtHI,  and ptH on the ATV61 and ATV71 drives exceed its maximum value of 65536 Hours

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Need to Reset Run time parameters after 7 years

Resolution:
When RTH, RTHI, PTH or PET value reaches 65535 (65535 hours = 2730 days = 7 years), the counter stays blocked at this value.
Also, It is impossible to reset PTH parameter.

Schneider Electric Australia

Explore more
Range:
Altivar 71Altivar 61
Explore more
Range:
Altivar 71Altivar 61
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.