GeoSCADA, SCADAPack - What does System Error Code 1410 indicate

The System Error Code -> 1410 on the controller status page of SCADAPack E Configurator indicates Low RAM battery.

GeoSCADA, SCADAPack - What does System Error Code 1410 indicate

You will have to replace the RAM battery to clear this error.

Replacing the RAM battery is discussed around page 141 onwards of the SCADAPack 535E Hardware Manual. This section also details the risks should the battery not be replaced. The Hardware Manual can be found at the following hyperlink:
-> https://www.se.com/au/en/download/document/SCADAPack%20535E_Hardware%20Manual/

Replacing the battery on a 535E
Schneider no longer supplies replacement RAM batteries. You can replace this battery with one of the following 3.6 V lithium batteries recommended by Schneider Electric when the rPAC reports that the RAM battery status is low and at the intervals recommended in the Routine Maintenance section.
· Tadiran TL-5186
· Omni Cell ER22G68
· Eve Energy ER22G68

After replacing the RAM batteries, kindly set the RTC to PC time and clear the system status code, from Transfer menu -> select Set RTU Time -> select Use local (PC) time and press ok.

Local on board RAM battery is monitored by binary system point 50207.

Schneider Electric Australia

GeoSCADA, SCADAPack - What does System Error Code 1410 indicate

 The System Error Code -> 1410 on the controller status page of SCADAPack E Configurator indicates Low RAM battery. 

 

GeoSCADA, SCADAPack - What does System Error Code 1410 indicate 

You will have to replace the RAM battery to clear this error. 

Replacing the RAM battery is discussed around page 141 onwards of the SCADAPack 535E Hardware Manual. This section also details the risks should the battery not be replaced. The Hardware Manual can be found at the following hyperlink:
-> https://www.se.com/au/en/download/document/SCADAPack%20535E_Hardware%20Manual/

Replacing the battery on a 535E 
Schneider no longer supplies replacement RAM batteries. You can replace this battery with one of the following 3.6 V lithium batteries recommended by Schneider Electric when the rPAC reports that the RAM battery status is low and at the intervals recommended in the Routine Maintenance section.
· Tadiran TL-5186
· Omni Cell ER22G68
· Eve Energy ER22G68

After replacing the RAM batteries, kindly set the RTC to PC time and clear the system status code, from Transfer menu -> select Set RTU Time -> select Use local (PC) time and press ok.

Local on board RAM battery is monitored by binary system point 50207.

Schneider Electric Australia

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.