{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

How can we help you today?

Modbus TCP register configuration with SoMove

1. Access Somove software, we will need to connect the drive to Somove. And find the menu in the below figure. if not sure how to, please see this video faq: https://www.youtube.com/watch?v=u6-CbjcifcU
Step1
2. Say we would like to add a read only "Motor Current" register in channel 3:
Step2
3. Right click the channel 3 area, click "add", find and select the "Motor current" option in the pop-up window. click "OK" to save and close the window.
Step3
4. The "Motor current" shows up in the main window, click the "Green tick" to save the change to the drive.
Step4
5. We can then access the "Motor current" parameter via Modbus TCP from the PLC side through channel 3.

Schneider Electric Australia

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: