{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Can the MotorLogic solid state overload relays be used on Open Delta or Grounded B-phase systems?

Issue:
Can 9065 Solid state overload relays be used in applications with Open Delta or Grounded B-phase systems?

Product Line:
NEMA Contactors and Overload relays


Environment:
9065 Motor Logic Solid-State Overload Relays


Cause:
The overload is tripping when used on Open Delta or Grounded B-phase systems


Resolution:
Open Delta systems or grounded B-phase systems are difficult to balance and could cause the Motor Logic SSOLR to trip. For these systems, it is better to use a Melting Alloy Overload Relay.

Schneider Electric Australia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: