Can I use iC60H3 RCBO to protect 2 phase loads(Balanced load 400-415V AC)?

Product Line:

iC60H3 RCBO

Resolution:

Yes , must connect to L2 & L3 phases since the test circuits are connected to them(See the schematic below). You will find the related information on Page 5 of the document CA902089 for the wiring of 3P IC60H3 RCBO .

schematic

Schneider Electric Australia

Attachment(s)
CA902089.pdf [1.96 MB]