{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

Does the Modbus Cradle Communication Module (CCM) support 2 wire RS485 communications?

Issue:
User may need to connect the CCM to a 2 wire daisy chain.

Product Line:
Cradle Communication Module

Environment:
RS-485 Communications

Resolution:
The Modbus Cradle Communications Module does support 2 wire RS485 communications. The module can be configured by jumpering the IN+ and the OUT+ and the IN- and the OUT-.

Schneider Electric Belgium

En savoir plus
Gamme :
MasterPact NTEasyPact MVSComPact NS NA
En savoir plus
Gamme :
MasterPact NTEasyPact MVSComPact NS NA