{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

How do you reset the fault over modbus on the ATS22 soft starter?

Issue:
Needs to reset the fault over modbus on the ATS22 soft starter.

Product Line:
Altistart ATS22

Environment:
All

Cause:
Fault reset over modbus

Resolution:
The CMD register is word 752.  If  you set bit 3 to a 1 on the CMD word  it will reset any resetable faults.

Schneider Electric Belgium

Pièce(s) jointe(s)

Modbus address words for the ATS22.pdfModbus address words for the ATS22.pdf [332.67 KB]
En savoir plus
Gamme :
En savoir plus
Gamme :