{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

Unable to configure GOOSE inputs for Vamp protection relays

Issue: Unable to configure GOOSE inputs for Vamp protection relays

Resolution: To be able to configure the GOOSE inputs for a VAMP relay you must select the Edition 2 Extensions check box when building the ICD file for the VAMP protection relay from VAMPset. This is what enables the GOOSE input configuration for the ICD file within VAMP SCD Editor.

Schneider Electric Belgium

En savoir plus
Gamme :
Vamp 50 SeriesVamp 200 SeriesVamp 40 SeriesVamp Measurement and Monitoring UnitsVamp 300 Series
En savoir plus
Gamme :
Vamp 50 SeriesVamp 200 SeriesVamp 40 SeriesVamp Measurement and Monitoring UnitsVamp 300 Series