{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

ATV312 Solar TF ( tank full ) fault. Please guide how to bypass tank full as liquid probe is not used for level sensing?

Tank Full " TF" is not a fault, it is a status indication in drive, which is arrived form the liquid probe, if installed.

If the customer is not using using liquid probe(water level sensor), they should change the parameter "LPA" to "NO". As default this parameter setting in drive is AI2, hence it should be changed to "NO" to avoid Tank Full "TF" indication. Refer the screen shot below for the parameter details.
parameter

Schneider Electric Belgium

En savoir plus
Gamme :
Altistart 22Altistart 48Altistart 01Altivar 71Altivar 61
En savoir plus
Gamme :
Altistart 22Altistart 48Altistart 01Altivar 71Altivar 61