{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

The Trend graph is not updating on the Magelis Runtime. How resolve the issue?

Issue:
The Trend graph is not updating on the Magelis Runtime.  How resolve the issue?

Product Line:
HMIGTO/GTU/STO/STU, XBTGC/GK/GT, iPC

Resolution:
It is possible that there are too many files in the storage drive.  It is recommended to format the storage device and redownload to the Magelis target.  On project download, please make sure to check the checkbox to  "Delete All Runtime Data".

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :