Power Monitoring Expert (PME) Alarm Annunciator Update rate

Issue
User would like to change interval for the Alarm banner update on the Web applications page of Power Monitoring Expert (PME)

Product
Power Monitoring Expert 8.x
Environment
Web Applications

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

1) Launch SQL Server Management Studio and connect to the instance where PME is running
2) Under Databases ->ApplicationModules -> Views, right click on [Configuration].[ConfigurationSettings] and select Edit top 200 rows
SQL Configuration.ConfigurationSettings

3) Look for the [Key] 'AlarmStatusUpdateIntervalSeconds' and change the value from 5 seconds to the desired update rate.
AlarmStatusUpdateIntervalSeconds

Note: reducing the interval below 5 seconds is not recommended and can lead to system performance issues.

Schneider Electric Belgium

Power Monitoring Expert (PME) Alarm Annunciator Update rate

Issue
User would like to change interval for the Alarm banner update on the Web applications page of Power Monitoring Expert (PME) 

Product
Power Monitoring Expert 8.x
Environment
Web Applications

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.* 

1) Launch SQL Server Management Studio and connect to the instance where PME is running
2) Under Databases ->ApplicationModules -> Views, right click on [Configuration].[ConfigurationSettings] and select Edit top 200 rows
SQL Configuration.ConfigurationSettings 

3) Look for the [Key] 'AlarmStatusUpdateIntervalSeconds' and change the value from 5 seconds to the desired update rate.
AlarmStatusUpdateIntervalSeconds 

Note: reducing the interval below 5 seconds is not recommended and can lead to system performance issues.

 

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
En savoir plus
Gamme :
En savoir plus
Gamme :
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.