Video: How can a factory reset be performed on an ATV320?

Article available in these languages: Czech, Finlandais, Japonais, Néerlandais

Issue:
Perform a factory reset on an ATV320 drive.

Product Line:
Altivar 320, ATV320

Environment:
All

Resolution:
To perform a factory reset from power up;
Enter on dial.
Scroll down to CONF menu and enter.
Scroll down to FCS- and enter.
Scroll down to FRY- and select all if you would like to reset all parameters (including function blocks). The two vertical lines to the right of 'all' should move up.
ESC back to FRY-.
Scroll down to GFS and enter.
Scroll down to yes and enter (hold for 3 seconds).
The parameter GFS should go to NO automatically.  This is when you know factory reset has been done.