{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

How to setup a run status on an ATS22 softstart?

Article available in these languages: Espagnol

Issue:
ATS22 run status setup

Product Line:
Altistart 22

Environment:
All

Cause:
Run status

Resolution:
Go into I/O menu.
Find R1 relay parameter.
R1 can be used as a run status.
R1 can be programmd to the following:
NSTP - starting - Relay is not energized at stop and is energized at all other times.
Run - running - Relay is energized when the bypass contactor is closed

Schneider Electric Belgium

En savoir plus
Gamme :
Altistart 22
En savoir plus
Gamme :
Altistart 22