{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

What is the difference between ACC and tLS when configuring ATS22 soft starter?

Article available in these languages: Espagnol

Issue:
Distinction between ACC and tLS parameters on ATS22.

Product Line:
Altistart 22 ATS22

Environment:
All

Cause:
There 2 different settings for the acceleration ramp time.

Resolution:
ACC [acceleration] = time to ramp from 0 to 60hz when a run command is given. The full inrush of the motor has to drop at the end of the ACC Ramp, before the motor is dropped to the shorting contactor. tLS [Max Start Time]  is time to ramp from 0 until the motor is dropped to the internal shorting contactor, thus has to be longer than ACC.

Schneider Electric Belgium

Pièce(s) jointe(s)

ATS48 Y Range basic.pdfATS48 Y Range basic.pdf [1.78 MB]
En savoir plus
Gamme :
Altistart 22
En savoir plus
Gamme :
Altistart 22