Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

What would cause the ATV600 or ATV900 to show Run 0.0hz if I'm not using anything external to adjust the speed?

Issue:
What would cause the ATV630 to show Run 0.0hz if I'm not using anything external to adjust the speed?

Product Line:
ATV630

Environment:
All


Cause:
Programming


Resolution:

If you're not using an external speed reference (i.e. Potentiometer, Transducer, etc.), when you close 24v to DI1 the drive shows 0.0hz.  You will need to go to [Simply Start] set [Low Speed] to 60hz (or desired speed)

Schneider Electric Belgium

En savoir plus
Catégorie :
AC Drives and Soft Starters
Gamme :
Altivar 71Altivar 61Altivar Process ATV600Altivar Process ATV900
En savoir plus
Catégorie :
AC Drives and Soft Starters
Gamme :
Altivar 71Altivar 61Altivar Process ATV600Altivar Process ATV900