{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
Is there possibility to assign temperature from PT100 to analog output on ATV630 or to read it by communication ?
Unfortunately this is not possible. Analog output cannot be assigned to motor temperature provided by PT100.
However TH2V value (AI2 thermal value when AI2 assigned to PT100) can be read by communication. Address 13250, range -15 .. + 200 degrees celsius.

Schneider Electric Belgium

En savoir plus
Gamme :
Articles utiles
En savoir plus
Gamme :