Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
How many SCADA clients can be connected to an Easergy T300 using IEC 104 protocol?
  • There is a limitation of 8 redundant connections to create multiple SCADA channels using the IEC104 protocol. Create 1 channel per client.
  • Make sure to fill-in the Remote IP@ list field. It shall be different for every channel
  • Please refer to attached file

Schneider Electric Belgium

Pièce(s) jointe(s)
How many SCADA clients can be connected to an Easergy T300 using IEC 104 protocol.pdf [313.34 KB]