{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
EBO SNVT types of third party devices doesnt match with SNVT types in TAC Vsta
EBO system processes data from third party LonWorks devices according definition by Device Template which is imported to a Building Operation Server (ES/AS-P).

In case SNVTs types visible in EBO don't match with SNVTs in TAC Vista database after conversion procedure was done, there must be discrepancy in XIF files which have been imported in advance.

Check up Network Variable index numbers for particular SNVTs which do not match after conversion against XIF files.

Make XIF file correction manually following LonMark org Technical Resource guide
http;//www.lonmark.org/technical_resources/resource_files/1500/snvt.pdf

Schneider Electric Belgium

En savoir plus
Gamme :
Articles utiles
En savoir plus
Gamme :