Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
image.png
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
  1. Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.
image.png
  1. Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.
image.png

Schneider Electric Belgium

PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
image.png
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
  1. Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.
image.png
  1. Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.
image.png

Schneider Electric Belgium

En savoir plus
Produit :
En savoir plus
Produit :
En savoir plus
Produit :
En savoir plus
Produit :
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.