Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
How to switch between Local and Remote modes on the remote graphic HMI connected to an ATV212?

Issue:

Switch to local mode on ATV212 using the remote keypad.

Product Line:

ATV212, S-Flex

Environment:

All models with VW3A1101 keypad connected

Cause:

Remote HMI does not have a LOC/REM button like the integral keypad.

Resolution:

The remote HMI, part# VW3A1101, has the F4 key assigned for LOC/REM switching. F4 toggles between LOC and REM modes. The active mode is indicated just above the F1 key.

Schneider Electric Belgium

En savoir plus
Gamme :
Articles utiles
En savoir plus
Gamme :