{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
Is the embedded NMC capable of reading or detecting the AP9613 dry contact when inserted into the Smart slot of the UPS?
Issue: Clarification about the accessory board (AP9613) and the embedded NMC

Product line: All Smart UPS with Embedded NMC and available Smart slot

Answer:
No!
The embedded NMC cannot detect or read the dry contact AP9613.

An embedded NMC as well as the removable/preinstalled NMC can only detect a dry contact which is directly connected to its I/O  port.

Embedded NMC and AP9613 Dry Contact.JPG

Schneider Electric Belgium

En savoir plus
Produit :
En savoir plus
Produit :