{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
HDPM6000 head unit is not displaying current readings

Issue

The HDPM6000 head unit is not reading current even though the CT's are wired to the unit.

Product Line

HDPM6000

Resolution

The HDPM6000 head unit requires voltage connections as well as current connections in order to read properly.  If only CT's are connected, the unit will not display values for current.  Voltage must also be connected to the unit in order for the current to be read.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.