{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Populaire vragen (FAQ's) zoeken
License Manager Shows Zero Devices and does not Allow New Product Key

Issue
License Manager shows zero devices for both 'current' and 'maximum' number of devices. When entering a new product key, it gives the following message:
Retrieving the com class factory, error 80040154

Product Line
PME 7.x.x
ION Enterprise 6.0

Resolution
The IONSNG.dll file needs to be registered:
1. Open a command prompt; navigate to ..\ION Enterprise\System\Bin folder
2. Type regsvr32 ionsng.dll and press 'Enter' key

Schneider Electric Belgium

Ontdek meer
Productfamilie
Mogelijk nuttige artikelen
Ontdek meer
Productfamilie