PowerScada Expert 7.20: "Failed to auto-login to server user. The user name or password are incorrect " Error on project startup.

This is what you will see in runtime if you have this issue
.Runtime Manager

You have to make sure the user name and password you define in the computer setup wizard as shown below are defined in your project or you can select the None option if you want all the processes to run from any user logged in to the server.
Configure Server