{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Populaire vragen (FAQ's) zoeken
Is it possible to configure a Form 9S 8600/8650 meter as a Form 35S?

Issue
Customer purchased a ION 8600/8650 with "Form Factor" of 9/29/36S Base and wants to wire as a Form 35S

Product Line
ION86xx

Environment
Installation and wiring

Cause
Customer purchased 9s meter for use in form 35S environment

Resolution
It is possible to configure a form 9S ION 8600/8650 meter as a form 35S, but a form 35S cannot be converted into a 9S since
the form 35S meter does not have a blade for I2 connection.

Following the diagrams below, the meters connection terminals can be rewired to match.

The 9S meter is normally configured as bellow to accept a 3 Element 4Wire-Wye system.
As you can see, the blade inputs are used to accept the I1/I2/I3 & V1/V2/V3/Vref inputs for the 9S. A 35S meter only uses I1/I3 & V1/V3/Vref to meter the Delta system.

Form 9 and 9SFrom 35 and 35S

The 9S can be modified easily to simulate the 35S measurement structure as below:
Wiring diagram

This can be done by modifying your 9S base meter wiring as the image below:
3 Element Form 9 and 9S

The meter's Volts mode configuration setting, found in the Basic Setup Parameters, needs to be changed to 35S 3-Wire instead of 9S 4-Wire.
The firmware is the same for all types of form factors hence, it is not required to change the firmware.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Mogelijk nuttige artikelen
Ontdek meer
Productfamilie