{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

ATV12 Can you have the run command from remote display and terminals?

Issue:
ATV12 run command in the remote display and the terminals.

Product Line:
Altivar 12

Cause:
Run the drive from 2 command sources

Resolution:
Yes it is possible:
Navigate to ConF- /   FULL- /  CtL- /  FR1 = LCC
Then to CON- / FLO = L1H

This configuration will start the drive from the remote display (the green RUN button) and if we close the contact on LI1.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie