{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

What would cause ground leakage current on an ATV61 or ATV71?

Issue:
What is the Ground leakage current for SCF3 fault?

Product Line:
Altivar 61, Altivar 71

Environment:
All

Cause:
Drive is tripping on SCF3 fault.

Resolution:
The threshold for a SCF3 fault (short-circuit to Ground) is 25% of drive nominal current. It is a hardware detection and it is not adjustable.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Altivar 71Altivar 61
Ontdek meer
Productfamilie
Altivar 71Altivar 61