Why can't I connect to my Magelis HMI with Web Gate with HTTPS?

Issue:
The Vijeo Designer Web Gate server does not support secure HTTP connections.

Product Line:
XBTGT, XBTGK, HMISTU, HMISTO, HMIGTO, HMIGK, HMIGTU, iPC

Resolution:
The Magelis HMIs do not support HTTPS (secure connections). Connect via Web Gate to the Magelis HMIs with HTTP only.