{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

What can cause an ETHF embedded ethernet com interrupt fault on the ATV630 and ATV930 process drives?

Issue:
Getting a ETHF embedded ethernet com interrupt fault on the ATV630 and ATV930 process drives.

Product Line:
ATV630 and ATV930 drive

Environment:
All with built in Ethernet

Cause:
Communication interruption on the Ethernet ModbusTCP bus.

Resolution:
Keep in mind that if the PLC or controller is not writing a command or reference to the drive within the programmed TTOB (Ethernet timeout or Hold up time) the Drive can trip on ETHF fault.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie