Unity Pro: coil not well animated on specfic LD network
On some very specific networks like below, the coil does not get the right value.
This problem comes when the Project Settings//General//Build settings//Generate with LD link animation
is not selected.


To work correctly the Project setting Generate with LD link animation must be checked.



This problem is corrected in Unity Pro V12.0.