How do I disable Output Phase Loss on an ATV320 drive?

Article available in these languages: Japans

Issue:
Disabling OPL on an ATV320 drive

Product Line:
Altivar 320

Environment:
All

Cause:
N/A

Resolution:
From the main menu enter and go down to CONF.
Enter and scroll down to FULL.
Enter and scroll down to FLT-
Enter and scroll down to OPL-
Enter and scroll down to opl.
Enter and adjust to no from yes to disable.
Enter to save setting.

See attachment