{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

What would cause a EPF2 fault using Profinet's telegram 1 and I/O profile on the ATV630 and ATV930 drives?

Issue:
EPF2 fault causes using Profinet and I/O profile on the ATV630 and ATV930 drives.

Product Line:
ATV630, ATV930

Environment:
All

Cause:
IO Profile and Telegram 1 are not compatible.

Resolution:
Profinet telegram 1 is not supported with IO Profile.  It is suggested that they use telegram 100 which does support IO Profile.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie