ATV6xx, ATV9xx when monitoring LCr (motor current) over communications, what feedback would you expect?

Article available in these languages: Spaans

Issue:
Expected feedback while monitoring LCr (motor current) over Communications.

Product Line:
ATV

Environment:
All

Cause:
Communication

Resolution:
LCR unit: [A]
drives up to     ..D15           coeff.: 0.01
drives:     D18..  to ..C16     coeff.: 0.1
drives higher than     C16..  coeff.: 1