{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

How can I define the communication period of my PowerTag Energy Sensor ?

Communication for PowerTag Energy Sensor is set by default to 5 seconds in wireless gateway. But to decrease Wireless traffic it is recommended  to increase this value according to Edge Control system needs (PLC, SCADA…).
Example: It is not usefull that the wireles gateway requests metering data for PowerTag Sensor every 5 seconds if SCADA requests only each 30 seconds the wireless gateway.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Acti9 PowerTag LinkPowerLogic™ PowerTag
Ontdek meer
Productfamilie
Acti9 PowerTag LinkPowerLogic™ PowerTag