Can I-line II busway be installed under a raised floor?

Issue:

Needs to install busway under a raised floor

Product Line:

Busway

Environment:

I-line II Busway

Cause:

N/A

Resolution:

Our I-Line II busway can be installed under "raised floors" as long as the busway joints and support system are accessible and the space is not used as return air systems.