My Micro DC came with clamp-on ferrites. Where do they go, and are there installation instructions?
Issue:
The Micro DC SX ships with clamp-on ferrites. I don't know where they go or how to install them.

Product Line:
Micro DC SX,

Environment:
24U and 48U SX EMEA units only

Cause:
The Micro Data Center SX International units ship with one snap-on ferrite per piece of installed equipment.

Resolution:
Ferrite is installed onto the network communications cable to reduce high frequency RF interference, and is required for 50 Hz operation.
See attachment for installation instructions.