{}

Nossas Marcas

Impact-Company-Logo-English Black-01-177x54

Bem-vindo ao website da Schneider Electric

Bem-vindo ao nosso site.
Pesquisar perguntas frequentes
Is it possible to have the NetShelter SX side panels open using the same key as the AR8132A?
Issue:
The AR8132A key will not lock or unlock the NetShelter SX side panels.

Product Line:
NetShelter SX, Colo

Environment:
All versions and serial ranges.

Cause:
The side panel uses a #333 key, but the AR8132A uses a #222 key.

Resolution:

The lock cylinders on the NetShelter SX side panels can be changed to match the key of the AR8132A.
To do so, please see FAQ FA158606: https://www.apc.com/us/en/faqs/FA158606/ This document will help you understand the different lock options available, and how to source them.

Schneider Electric Brasil

Conheça mais
Linha:
Artigos que podem ser úteis
Conheça mais
Linha: