Are the NetShelter VX Seismic cabinets and 2-Post Racks OSHPD compliant?
Issue:
the question has been risen if a NetShelter VX Seismic cabinet is OSHPD compliant.

Product Line:
NetShelter VX Seismic, 2-Post Rack

Environment:
AR2144BLK, AR2145BLK, AR201: all serial ranges.

Cause:
The only seismic documents on the product pages of AR2144BLK and AR2145BLK are the NEBS GR-63-CORE Zone 4.
There are no seismic documents on the product page of AR201.

Resolution:

Several Smart-UPS were tested and approved for installation with NetShelter VX Seismic and AR201 during OSHPD Special Seismic Preapproval (OSP) testing. Please see the attachment.