Smart UPS Modular Ultra A7A1 Power Module Error
Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

If you see an “A7A1” error on a Power Module, please do not replace the Power Module in question.  This error code occurs when there is a PM with firmware 3.3 (or later) and it cannot get an appropriate response from the IM running with UPS firmware 10.8.  To fix this issue, please upgrade the UPS to 13.2 (or later).  Please follow the process below to upgrade the Firmware.

If the issue persists after upgrading the firmware, please get the Power Module replaced.


NMC/Display Firmware - https://www.apc.com/us/en/faqs/FAQ000261841/
UPS Firmware - https://www.apc.com/us/en/faqs/FAQ000261838/
Different ways to Upgrade UPS Firmware - https://www.apc.com/us/en/faqs/FA164737/

Schneider Electric Brasil

Smart UPS Modular Ultra A7A1 Power Module Error
Product Line: 

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

If you see an “A7A1” error on a Power Module, please do not replace the Power Module in question.  This error code occurs when there is a PM with firmware 3.3 (or later) and it cannot get an appropriate response from the IM running with UPS firmware 10.8.  To fix this issue, please upgrade the UPS to 13.2 (or later).  Please follow the process below to upgrade the Firmware.  

If the issue persists after upgrading the firmware, please get the Power Module replaced.  


NMC/Display Firmware - https://www.apc.com/us/en/faqs/FAQ000261841/
UPS Firmware - https://www.apc.com/us/en/faqs/FAQ000261838/
Different ways to Upgrade UPS Firmware - https://www.apc.com/us/en/faqs/FA164737/

 

Schneider Electric Brasil

Conheça mais
Produto:
Conheça mais
Produto:
Conheça mais
Produto:
Conheça mais
Produto:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.