APC Symmetra LX (REPO) Remote Emergency Power Off Wiring Instructions

Issue:

If required, a Remote Emergency Power Off (REPO) function can be connected to the Symmetra LX. It is a critical safety feature that allows for the immediate shutdown of power to the electrical equipment in emergency situations. When wiring a Symmetra LX UPS for REPO, it's essential to adhere to all safety guidelines and local electrical codes.


Product Line:

Symmetra LX


Environment:

All serial numbers


Cause:

The purpose of this document is to provide users with a wiring guide for implementing the REPO (Remote Emergency Power Off) feature on a Symmetra LX UPS.

Note: In many locations, the Remote Emergency Power Off (REPO) switch must be installed by a licensed electrician. Refer to local and national codes. See the Symmetra LX Safety and General Information Guide or the attached file for REPO requirements and detailed safety instructions.


Resolution:

Symmetra LX REPO Guide

Schneider Electric Brasil

Anexo(s)
Symmetra LX Safety and General Information Guide.pdf [712.83 KB]
APC Symmetra LX (REPO) Remote Emergency Power Off Wiring Instructions

Issue:

If required, a Remote Emergency Power Off (REPO) function can be connected to the Symmetra LX. It is a critical safety feature that allows for the immediate shutdown of power to the electrical equipment in emergency situations. When wiring a Symmetra LX UPS for REPO, it's essential to adhere to all safety guidelines and local electrical codes.


Product Line:

Symmetra LX


Environment:

All serial numbers


Cause:

The purpose of this document is to provide users with a wiring guide for implementing the REPO (Remote Emergency Power Off) feature on a Symmetra LX UPS.

Note: In many locations, the Remote Emergency Power Off (REPO) switch must be installed by a licensed electrician. Refer to local and national codes. See the Symmetra LX Safety and General Information Guide or the attached file for REPO requirements and detailed safety instructions. 


Resolution:

Symmetra LX REPO Guide

Schneider Electric Brasil

Anexo(s)
Symmetra LX Safety and General Information Guide.pdf [712.83 KB]
Conheça mais
Linha:
Conheça mais
Linha:
Conheça mais
Linha:
Conheça mais
Linha:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.